Normal view

There are new articles available, click to refresh the page.
Before yesterdayAll CISA Advisories

Rockwell Automation FactoryTalk Linx

By: CISA
16 October 2025 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.5
  • ATTENTION: Low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: FactoryTalk Linx
  • Vulnerabilities: Privilege Chaining

2. RISK EVALUATION

Successful exploitation of these vulnerabilities may allow full access to all files, processes, and system resources.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Rockwell Automation reports that the following versions of the FactoryTalk Linx control system data communications platform are affected:

  • FactoryTalk Linx: Versions 6.40 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1 PRIVILEGE CHAINING CWE-268

A security issue exists within the x86 Microsoft Installer File (MSI), which is installed with FTLinx. Authenticated attackers with valid Windows user credentials can initiate a repair and hijack the resulting console window. This allows the launching of a command prompt running with SYSTEM-level privileges, which provides full access to all files, processes, and system resources.

CVE-2025-9067 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-9067. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 PRIVILEGE CHAINING CWE-268

A security issue exists within the Rockwell Automation Driver Package x64 Microsoft Installer File (MSI) repair functionality, which is installed with FTLinx. Authenticated attackers with valid Windows user credentials can initiate a repair and hijack the resulting vbpinstall.exe console window. This allows the launching of a command prompt with SYSTEM-level privileges, granting full access to all files, processes, and system resources.

CVE-2025-9068 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-9068. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported these vulnerabilities to CISA.

4. MITIGATIONS

Rockwell Automation recommends users of the affected software consider installing the Microsoft patch to address the MSI issue. If possible, users should also upgrade to version 6.50 or later. Users of the affected software unable to upgrade to one of the corrected versions should follow Rockwell Automation's security best practices.

For more information, see Rockwell Automation's security advisory SD1754.

CISA recommends users take the following measures to protect themselves from social engineering attacks:

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.

5. UPDATE HISTORY

  • October 16, 2025: Initial Republication of Rockwell Automation's security advisory SD1754.

Siemens TeleControl Server Basic

By: CISA
16 October 2025 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: TeleControl Server Basic
  • Vulnerability: Missing Authentication for Critical Function

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to obtain password hashes of users and to login to and perform authenticated operations of the database service.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • TeleControl Server Basic V3.1: Version V3.1.2.2 and up to but not including V3.1.2.3

3.2 VULNERABILITY OVERVIEW

3.2.1 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306

The affected application contains an information disclosure vulnerability. This could allow an unauthenticated remote attacker to obtain password hashes of users and to login to and perform authenticated operations of the database service.

CVE-2025-40765 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-40765. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Tenable reported this vulnerability to Siemens.
Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • TeleControl Server Basic V3.1: Restrict access to port 8000 on the affected systems to trusted IP addresses only
  • TeleControl Server Basic V3.1: Update to V3.1.2.3 or later version

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-062309 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 16, 2025: Initial Republication of Siemens ProductCERT SSA-062309

Siemens SiPass Integrated

By: CISA
16 October 2025 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.6
  • ATTENTION: Low attack complexity
  • Vendor: Siemens
  • Equipment: SiPass integrated
  • Vulnerabilities: Improper Restriction of Operations within the Bounds of a Memory Buffer, Cross-site Scripting, Authorization Bypass Through User-Controlled Key, Storing Passwords in a Recoverable Format

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an unauthenticated remote attacker to gain unauthorized access to user accounts, manipulate data, impersonate users, or execute arbitrary code on the SiPass integrated server.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • SiPass integrated: Versions prior to V3.0

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

A heap-based buffer overflow vulnerability exists in the pictwread functionality of Accusoft ImageGear 20.1. A specially crafted, malformed file can lead to arbitrary code execution. An attacker can provide a malicious file to trigger this vulnerability.

CVE-2023-35002 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2023-35002. A base score of 8.6 has been calculated; the CVSS vector string is (CVSS:4.0/AV:A/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION ('CROSS-SITE SCRIPTING') CWE-79

Affected server applications are vulnerable to stored cross-site scripting (XSS), which allows an attacker to inject malicious code that can be executed by other users when they visit the affected page. Successful exploitation enables an attacker to impersonate other users within the application and steal their session data. This could enable unauthorized access to accounts and potentially lead to privilege escalation.

CVE-2025-40772 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:A/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-40772. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:A/AC:L/AT:N/PR:L/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.3 AUTHORIZATION BYPASS THROUGH USER-CONTROLLED KEY CWE-639

Affected server applications contain a broken access control vulnerability. The authorization mechanisms lack sufficient server-side checks, which allows an attacker to execute specific API requests. Successful exploitation may allow an attacker to manipulate data belonging to other users.

CVE-2025-40773 has been assigned to this vulnerability. A CVSS v3.1 base score of 3.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:A/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:N).

A CVSS v4 score has also been calculated for CVE-2025-40773. A base score of 5.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:A/AC:L/AT:N/PR:L/UI:N/VC:N/VI:L/VA:N/SC:N/SI:N/SA:N).

3.2.4 STORING PASSWORDS IN A RECOVERABLE FORMAT CWE-257

Affected server applications store user passwords in an encrypted format in their databases. Decryption keys are accessible to users with administrative privileges, which allows them to recover passwords. Successful exploitation of this vulnerability enables an attacker to obtain and use valid user passwords. This can lead to unauthorized access to user accounts, data breaches, and potential system compromise.

CVE-2025-40774 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2025-40774. A base score of 6.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:H/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Thomas Wache and Yann Breut from Airbus Defence and Space - Cyber Program reported one of the vulnerabilities to Siemens.

4. MITIGATIONS

Siemens has released a new version for SiPass integrated and recommends updating to the latest version:

  • Update to V3.0 or a later version.
  • Restrict access to authorized and trusted personnel only.
  • Avoid uploading untrusted image files in affected applications.

As a general security measure, Siemens strongly recommends protecting network access to affected products with appropriate mechanisms. It is advised to follow recommended security practices in order to run the devices in a protected IT environment.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-599451 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as virtual private networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.

5. UPDATE HISTORY

  • October 16, 2025: Initial Republication of Siemens SSA-599451

Rockwell Automation ArmorStart AOP

By: CISA
16 October 2025 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: ArmorStart AOP
  • Vulnerability: Uncaught Exception

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition on the affected product.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Rockwell Automation products are affected:

  • ArmorStart AOP: Version V2.05.07 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1 Uncaught Exception CWE-248

A security issue exists within the Studio 5000 Logix Designer add-on profile (AOP) for the ArmorStart Classic distributed motor controller, resulting in a denial-of-service. This vulnerability is possible due to the input of invalid values into Component Object Model (COM) methods.

CVE-2025-9437 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-9437. A base score of 8.7 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported this vulnerability to CISA.

4. MITIGATIONS

Rockwell Automation reports there is no fix available and recommends users of the affected product follow security best practices.

For more information, visit Rockwell Automation Security Advisories.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 16, 2025: Initial Republication of Rockwell Automation Security Advisory SD1751

CISA Releases Thirteen Industrial Control Systems Advisories

By: CISA
16 October 2025 at 08:00

CISA released thirteen Industrial Control Systems (ICS) advisories on October 16, 2025. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS.

CISA encourages users and administrators to review newly released ICS advisories for technical details and mitigations.

Rockwell Automation FactoryTalk ViewPoint

By: CISA
16 October 2025 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: FactoryTalk ViewPoint
  • Vulnerability: Improper Restriction of XML External Entity Reference

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow unauthenticated attackers to achieve XML external entity injection, resulting in a temporary denial-of-service condition.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Rockwell Automation reports the following versions of PanelView Plus (which interacts with FactoryTalk ViewPoint) are affected by this vulnerability:

  • PanelView Plus 7 Terminal: Version 14 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1 Improper Restriction of XML External Entity Reference CWE-611

A security issue was discovered within FactoryTalk ViewPoint, allowing unauthenticated attackers to achieve XML external entity injection. Certain SOAP requests can be abused resulting in a temporary denial-of-service.

CVE-2025-9066 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-9066. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Energy, Food and Agriculture, Transportation Systems, and Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported this vulnerability to CISA.

4. MITIGATIONS

Rockwell Automation recommends that users upgrade to one of the following versions:

  • Panel View Plus 7 Standard and Panel View Plus 7 Performance Series A v12, v13, v14 patch AID BF30506 (firmware fix)
  • Panel View Plus 7 Performance Series B V14.103

Users of the affected software who are unable to upgrade to one of the corrected versions should use Rockwell Automation's security best practices.

For more information, see the Rockwell Automation advisory SD1752 for this vulnerability.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 16, 2025: Initial Republication of Rockwell Automation security advisory SD1752

Siemens SINEC NMS

By: CISA
16 October 2025 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SINEC NMS
  • Vulnerability: Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection')

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an authenticated low privileged attacker to insert malicious data and achieve privilege escalation.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • SINEC NMS: Versions prior to V4.0 SP1

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89

Affected applications are vulnerable to SQL injection through getTotalAndFilterCounts endpoint. An authenticated low privileged attacker could exploit to insert data and achieve privilege escalation. (ZDI-CAN-26570)

CVE-2025-40755 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-40755. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens ProductCERT reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-318832 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 16, 2025: Initial Republication of Siemens ProductCERT SSA-318832

Rockwell Automation FactoryTalk View Machine Edition and PanelView Plus 7

By: CISA
16 October 2025 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: FactoryTalk View Machine Edition and PanelView Plus 7
  • Vulnerabilities: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal'), Improper Authorization

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an unauthenticated attacker to access to the device's file system.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Rockwell Automation FactoryTalk View Machine Edition and PanelView Plus 7 are affected:

  • FactoryTalk View Machine Edition: Versions prior to V15.00 (CVE-2025-9064)
  • PanelView Plus 7: Version V14.100 (CVE-2025-9063)

3.2 VULNERABILITY OVERVIEW

3.2.1 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') CWE-22

A path traversal security issue exists within FactoryTalk View Machine Edition, allowing unauthenticated attackers on the same network as the device to delete any file within the panels operating system. Exploitation of this vulnerability is dependent on the knowledge of filenames to be deleted.

CVE-2025-9064 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-9064. A base score of 8.7 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.2.2 Improper Authorization CWE-285

An authentication bypass security issue exists within FactoryTalk View Machine Edition Web Browser ActiveX control. Exploitation of this vulnerability allows unauthorized access to the PanelView Plus 7 Series B, including access to the file system, retrieval of diagnostic information, event logs, and more.

CVE-2025-9063 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:L/A:H).

A CVSS v4 score has also been calculated for CVE-2025-9063. A base score of 7 has been calculated; the CVSS vector string is (AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:L/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported these vulnerabilities to CISA.

4. MITIGATIONS

Rockwell Automation encourages users of the affected software to apply the following risk mitigations, if possible:

For CVE-2025-9064, update FactoryTalk View ME V15.00 and later on ASEM 6300 IPC's-Patch BF31001.

For CVE-2025-9063 and CVE-2025-9064, update PanelView Plus 7 Performance Series B V14.103 firmware package.

Rockwell Automation encourages users of the affected software who are unable to upgrade to one of the corrected versions to follow Rockwell Automation's security best practices.

For more information, visit Rockwell Automation Security Advisories for more information.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 16, 2025: Initial Republication of Rockwell Automation's advisory

Siemens SIMATIC ET 200SP Communication Processors

By: CISA
16 October 2025 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SIMATIC ET 200SP
  • Vulnerability: Missing Authentication for Critical Function

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to access the configuration data.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Siemens SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0): vers:intdot/<2.4.24
  • Siemens SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0): vers:intdot/<2.4.24
  • Siemens SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0): vers:intdot/<2.4.24
  • Siemens SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0): vers:intdot/<2.4.24
  • Siemens SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0): vers:intdot/<2.4.24
  • Siemens SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0): vers:intdot/<2.4.24

3.2 VULNERABILITY OVERVIEW

3.2.1 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306

Affected devices do not properly authenticate configuration connections. This could allow an unauthenticated remote attacker to access the configuration data.

CVE-2025-40771 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-40771. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens ProductCERT reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • All affected products: Restrict access to the affected systems to trusted IP addresses only
  • All affected products: Update to V2.4.24 or later version

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-486936 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 16, 2025: Initial Republication of Siemens ProductCERT SSA-486936

Siemens HyperLynx and Industrial Edge App Publisher

By: CISA
16 October 2025 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.0
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: HyperLynx and Industrial Edge App Publisher
  • Vulnerability: Access of Resource Using Incompatible Type ('Type Confusion')

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow a remote attacker to perform arbitrary code execution via a crafted HTML page.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Siemens HyperLynx: vers:all/*
  • Siemens Industrial Edge App Publisher: vers:intdot/<1.23.5

3.2 VULNERABILITY OVERVIEW

3.2.1 ACCESS OF RESOURCE USING INCOMPATIBLE TYPE ('TYPE CONFUSION') CWE-843

Type confusion in V8 in Google Chrome prior to 138.0.7204.96 allowed a remote attacker to perform arbitrary read/write via a crafted HTML page. (Chromium security severity: High) For HyperLynx: An attacker would need to modify local files and need access to the application in order to exploit.

CVE-2025-6554 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.1 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2025-6554. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:P/PR:H/UI:A/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).

3.3 PRODUCT IMPACT

Product-specific impact for an affected product vulnerable to the CVE:

3.4 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.5 RESEARCHER

Siemens ProductCERT reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • HyperLynx: Currently no fix is available
  • Industrial Edge App Publisher: Update to V1.23.5 or later version

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-365200 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 16, 2025: Initial Republication of Siemens ProductCERT SSA-365200

Hitachi Energy MACH GWS

By: CISA
16 October 2025 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.1
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Hitachi Energy
  • Equipment: MACH GWS
  • Vulnerabilities: Incorrect Default Permissions, Improper Validation of Integrity Check Value, Improper Certificate Validation

2. RISK EVALUATION

Exploiting these vulnerabilities could allow an attacker to tamper with system files, cause a denial of service, or perform a remote man-in-the-middle attack.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of MACH GWS affected:

  • MACH GWS: Versions 3.0.0.0 to 3.4.0.0

3.2 VULNERABILITY OVERVIEW

3.2.1 INCORRECT DEFAULT PERMISSIONS CWE-276

A vulnerability exists in MACH GWS product, which if exploited, could allow a local unauthenticated attacker to tamper a system file resulting in a denial of notify service.

CVE-2025-39201 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.1 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:H).

A CVSS v4 score has also been calculated for CVE-2025-39201. A base score of 6.9 has been calculated; the CVSS vector string is (AV:L/AC:L/AT:N/PR:L/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:L).

3.2.2 IMPROPER VALIDATION OF INTEGRITY CHECK VALUE CWE-354

A vulnerability exists in the IEC 61850 of the MACH GWS product where an IEC 61850-8 crafted message content from IED or remote system can cause a denial of service resulting in disconnection loop.

CVE-2025-39203 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-39203. A base score of 7.1 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.2.3 IMPROPER CERTIFICATE VALIDATION CWE-295

A vulnerability exists in the IEC 61850 in MACH GWS product where the certificate validation of the TLS protocol allows a remote man-in-the-middle attack due to missing proper validation.

CVE-2025-39205 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2025-39205. A base score of 7.1 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Switzerland

3.4 RESEARCHER

Hitachi Energy PSIRT reported these vulnerabilities to CISA.

4. MITIGATIONS

Hitachi Energy recommends users update to Version 3.5 at the earliest.

Hitachi Energy recommends the following security practices and firewall configurations to help protect a process control network from attacks that originate from outside the network. Such practices include ensuring that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system. Proper password policies and processes should be followed.

Hitachi Energy recommends users deploy the product following the "GWS deployment guideline" document. Users should maintain their systems with products running on supported versions and follow maintenance releases.

For more information see the associated Hitachi Energy PSIRT security advisory 8DBD000222 Multiple Vulnerabilities in Hitachi Energy MACH GWS Product.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 16, 2025: Initial Republication of Hitachi Energy PSIRT 8DBD000222

Siemens Solid Edge

By: CISA
16 October 2025 at 08:00

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.3
  • ATTENTION: Low Attack Complexity
  • Vendor: Siemens
  • Equipment: Solid Edge
  • Vulnerabilities: Out-of-bounds Write, Out-of-bounds Read

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to crash the application or execute arbitrary code.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Siemens Solid Edge SE2024: All versions < V224.0 Update 14
  • Siemens Solid Edge SE2025: All versions < V225.0 Update 6

3.2 VULNERABILITY OVERVIEW

3.2.1 OUT-OF-BOUNDS WRITE CWE-787

The affected applications contain an out of bounds write vulnerability while parsing specially crafted PRT files. This could allow an attacker to crash the application or execute code in the context of the current process.

CVE-2025-40809 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-40809. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 OUT-OF-BOUNDS WRITE CWE-787

The affected applications contain an out of bounds write vulnerability while parsing specially crafted PRT files. This could allow an attacker to crash the application or execute code in the context of the current process.

CVE-2025-40810 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-40810. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.3 OUT-OF-BOUNDS READ CWE-125

The affected applications contain an out of bounds read vulnerability while parsing specially crafted PRT files. This could allow an attacker to crash the application or execute code in the context of the current process.

CVE-2025-40811 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-40811. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.4 OUT-OF-BOUNDS READ CWE-125

The affected applications contain an out of bounds read vulnerability while parsing specially crafted PRT files. This could allow an attacker to crash the application or execute code in the context of the current process.

CVE-2025-40812 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-40812. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Michael Heinzl reported these vulnerabilities to Siemens ProductCERT. Siemens ProductCERT reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • All affected products: Do not open untrusted PRT files in affected applications
  • Solid Edge SE2024: Update to V224.0 Update 14 or later version
  • Solid Edge SE2025: Update to V225.0 Update 6 or later version

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-541582 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.

5. UPDATE HISTORY

  • October 14, 2025: Initial Republication of Siemens ProductCERT SSA-541582

CISA Directs Federal Agencies to Mitigate Vulnerabilities in F5 Devices

By: CISA
15 October 2025 at 08:00

Today, CISA issued Emergency Directive ED 26-01: Mitigate Vulnerabilities in F5 Devices to direct Federal Civilian Executive Branch agencies to inventory F5 BIG-IP products, evaluate if the networked management interfaces are accessible from the public internet, and apply newly released updates from F5. 

A nation-state affiliated cyber threat actor has compromised F5 systems and exfiltrated data, including portions of the BIG-IP proprietary source code and vulnerability information, which provides the actor with a technical advantage to exploit F5 devices and software. This poses an imminent threat to federal networks using F5 devices and software.

Key Actions Required:

  • Inventory: Identify all instances of F5 BIG-IP hardware devices and F5OS, BIG-IP TMOS, Virtual Edition, BIG-IP Next, BIG-IP IQ software, and BNK / CNF.
  • Harden Public-Facing Hardware and Software Appliances: Identify if physical or virtual BIG-IP devices exposed to the public internet provide public access to the networked management interface.
  • Update Instances of BIG-IP Hardware and Software Applications: Apply the latest vendor updates by Oct. 22, 2025, for the following products: F5OS, BIG-IP TMOS, BIG-IQ, and BNK / CNF— validate the F5 published MD5 checksums for its software image files and other F5 downloaded software. For other devices, update with the latest software release by Oct. 31, 2025, and apply the latest F5-provided asset hardening guidance.
  • Disconnect End of Support Devices: Disconnect all public-facing F5 devices that have reached their end-of-support date. Report mission-critical exceptions to CISA.
  • Mitigate Against Cookie Leakage: If CISA notifies an agency of a BIG-IP cookie leakage vulnerability, the agency shall follow CISA’s accompanying mitigation instructions.
  • Report: Submit a complete inventory of F5 products and actions taken to CISA by 11:59 p.m. EDT, Oct. 29, 2025.

For detailed guidance, refer to the full Emergency Directive ED 26-01.

CISA Adds One Known Exploited Vulnerability to Catalog

By: CISA
15 October 2025 at 08:00

CISA has added one new vulnerability to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation.

  • CVE-2025-54253 Adobe Experience Manager Forms Code Execution Vulnerability

This type of vulnerability is a frequent attack vector for malicious cyber actors and poses significant risks to the federal enterprise. 

Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.

Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of KEV Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.

CISA Releases One Industrial Control Systems Advisory

By: CISA
14 October 2025 at 08:00

CISA released one Industrial Control Systems (ICS) advisory on October 14, 2025. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS.

CISA encourages users and administrators to review newly released ICS advisories for technical details and mitigations.

Rockwell Automation 1715 EtherNet/IP Comms Module

By: CISA
14 October 2025 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: 1715 EtherNet/IP
  • Vulnerabilities: Allocation of Resources Without Limits or Throttling, Out-of-bounds Write

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to cause the web server to crash, requiring a restart to recover.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Rockwell Automation 1715 EtherNet/IP Comms Module are affected:

  • 1715 EtherNet/IP: Versions 3.003 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1 ALLOCATION OF RESOURCES WITHOUT LIMITS OR THROTTLING CWE-770

A denial-of-service security issue exists in the affected product and version. The security issue stems from a high number of requests sent to the web server. This could result in a web server crash; however, this does not impact I/O control or communication. A power cycle is required to recover and utilize the webpage.

CVE-2025-9177 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-9177. A base score of 7.7 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:N/SC:N/SI:N/SA:H).

3.2.2 OUT-OF-BOUNDS WRITE CWE-787

A denial-of-service security issue exists in the affected product and version. The security issue is caused through CIP communication using crafted payloads. The security issue could result in no CIP communication with 1715 EtherNet/IP Adapter. A restart is required to recover.

CVE-2025-9178 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-9178. A base score of 7.7 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:N/SC:N/SI:N/SA:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported these vulnerabilities to CISA.

4. MITIGATIONS

Rockwell Automation has released the following for user implementation:

Users of the affected software who are unable to upgrade to one of the corrected versions should apply Rockwell Automation's security best practices.

For more information, see Rockwell Automation's advisory SD1757.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 14, 2025: Initial Republication of Rockwell Automation advisory SD1757

CISA Adds Five Known Exploited Vulnerabilities to Catalog

By: CISA
14 October 2025 at 08:00

CISA has added five new vulnerabilities to its Known Exploited Vulnerabilities (KEV) Catalog, based on evidence of active exploitation.

  • CVE-2016-7836 SKYSEA Client View Improper Authentication Vulnerability
  • CVE-2025-6264 Rapid7 Velociraptor Incorrect Default Permissions Vulnerability
  • CVE-2025-24990 Microsoft Windows Untrusted Pointer Dereference Vulnerability
  • CVE-2025-47827 IGEL OS Use of a Key Past its Expiration Date Vulnerability
  • CVE-2025-59230 Microsoft Windows Improper Access Control Vulnerability

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.

Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the KEV Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.

Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of KEV Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.

Hitachi Energy Asset Suite

By: CISA
9 October 2025 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 6.0
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Hitachi Energy
  • Equipment: Asset Suite
  • Vulnerability: Improper Output Neutralization for Logs

2. RISK EVALUATION

Successful exploitation of this vulnerability could result in the manipulation of content or the injection of data with the potential of carrying out further malicious attacks.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Asset Suite are affected:

  • Asset Suite: Versions 9.7 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER OUTPUT NEUTRALIZATION FOR LOGS CWE-117

A vulnerability exists in Asset Suite for an authenticated user to manipulate the content of performance related log data or to inject crafted data in logfile for potentially carrying out further malicious attacks. Performance logging is typically enabled for troubleshooting purposes while resolving application performance related issues.

CVE-2025-10217 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2025-10217. A base score of 6.0 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:P/PR:L/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Switzerland

3.4 RESEARCHER

Hitachi Energy PSIRT reported this vulnerability to CISA.

4. MITIGATIONS

Hitachi Energy recommends users disable performance logging and apply the update as soon as it becomes available.

Hitachi Energy recommends the following security practices and firewall configurations to help protect a process control network from attacks originating from outside the network. Such practices include ensuring process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system with a minimal number of exposed ports, and others to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system. Proper password policies and processes should be followed.

For more information see the associated Hitachi Energy PSIRT security advisory Log Data Vulnerability in Hitachi Energy Asset Suite Product.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 9, 2025: Initial Republication of Hitachi Energy PSIRT 8DBD000226

Rockwell Automation Stratix

By: CISA
9 October 2025 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 6.3
  • ATTENTION: Exploitable remotely/Low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: Stratix 5700, 5400, 5410, 5200, 5800
  • Vulnerability: Stack-based Buffer Overflow

2. RISK EVALUATION

Successful exploitation of this vulnerability could result in arbitrary code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following version of Stratix 5700 is affected:

  • Stratix 5700: Version v15.2(8)E7 and prior
  • Stratix 5400: Version v15.2(8)E7 and prior
  • Stratix 5410: Version v15.2(8)E7 and prior
  • Stratix 5200: Version v17.17.01 and prior
  • Stratix 5800: Version v17.17.01 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1 STACK-BASED BUFFER OVERFLOW CWE-121

A third-party vulnerability exists in the affected products. The affected products use Cisco IOS XE Software which contains a vulnerability in the Simple Network Management Protocol (SNMP) subsystem. An authenticated, remote attacker with low privileges could cause a denial-of-Service (DoS) condition on an affected device running Cisco IOS Software or Cisco IOS XE Software. To cause the DoS, the attacker must have the SNMPv2c or earlier read-only community string or valid SNMPv3 user credentials. An authenticated, remote attacker with high privileges could execute code as the root user on an affected device running Cisco IOS XE Software. To execute code as the root user, the attacker must have the SNMPv1 or v2c read-only community string or valid SNMPv3 user credentials and administrative or privilege 15 credentials on the affected device. An attacker could exploit this vulnerability by sending a crafted SNMP packet to an affected device over IPv4 or IPv6 networks. This vulnerability is due to a stack overflow condition in the SNMP subsystem of the affected software. A successful exploit could allow a low-privileged attacker to cause the affected system to reload, resulting in a DoS condition, or allow a high-privileged attacker to execute arbitrary code as the root user and obtain full control of the affected system.

CVE-2025-20352 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:C/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-20352. A base score of 6.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:N/SC:N/SI:N/SA:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported this vulnerability to CISA.

4. MITIGATIONS

Rockwell Automation recommends users of the affected Stratix software implement workarounds from Cisco and our security best practices.

For more information about this issue, see the advisory on the Rockwell Automation security page.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 09, 2025: Initial Republication of Rockwell Automation advisory SD1749

Rockwell Automation Lifecycle Services with Cisco

By: CISA
9 October 2025 at 08:00

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 6.3
  • ATTENTION: Exploitable remotely/Low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: Industrial Data Center (IDC) with Cisco Switching, IDC-Managed Support contract with Cisco Switching, Network-Managed Support contract with Cisco network switch, Firewall-Managed Support contract with Cisco firewall
  • Vulnerability: Stack-based Buffer Overflow

2. RISK EVALUATION

Successful exploitation of this vulnerability could result in arbitrary code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Rockwell Automation reports the following Lifecycle Services with Cisco are affected:

  • Industrial Data Center (IDC) with Cisco Switching: Generations 1 - 5
  • IDC-Managed Support contract with Cisco Switching: Generations 1 - 5
  • Network-Managed Support contract with Cisco network switch: All versions
  • Firewall-Managed Support contract with Cisco firewall: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 STACK-BASED BUFFER OVERFLOW CWE-121

A third-party vulnerability exists in the affected products. The affected products use Cisco IOS XE Software which contains a vulnerability in the Simple Network Management Protocol (SNMP) subsystem. An authenticated, remote attacker with low privileges could cause a denial-of-service (DoS) condition on an affected device running Cisco IOS Software or Cisco IOS XE Software. To cause the DoS, the attacker must have the SNMPv2c or earlier read-only community string or valid SNMPv3 user credentials. An authenticated, remote attacker with high privileges could execute code as the root user on an affected device running Cisco IOS XE Software. To execute code as the root user, the attacker must have the SNMPv1 or v2c read-only community string or valid SNMPv3 user credentials and administrative or privilege 15 credentials on the affected device. An attacker could exploit this vulnerability by sending a crafted SNMP packet to an affected device over IPv4 or IPv6 networks. This vulnerability is due to a stack overflow condition in the SNMP subsystem of the affected software. A successful exploit could allow a low-privileged attacker to cause the affected system to reload, resulting in a DoS condition, or allow a high-privileged attacker to execute arbitrary code as the root user and obtain full control of the affected system.

CVE-2025-20352 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:C/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-20352. A base score of 6.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:N/SC:N/SI:N/SA:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported this vulnerability to CISA.

4. MITIGATIONS

Rockwell Automation recommends users take the following actions based on their situation.

Users with an active Rockwell Automation Infrastructure Managed Service contract:

  • Contact Rockwell Automation to discuss actions needed for remediation efforts

Users without a Rockwell Automation managed services contract, refer to Cisco's workarounds below:

Additionally, users of the affected software who are unable to upgrade to one of the corrected versions are encouraged to apply security best practices, where possible.

For more information about this issue, see the advisory on the Rockwell Automation security page.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY